The 3-Phase Power Meter / 3-Phase Power Analyzer measures current and voltage values using the connected current transformers and test leads. From this, the active, apparent and reactive power are determined and transmitted to the measuring platform every second via Wi-Fi. The data is then filed historically on the 3-Phase Power Meter / 3-Phase Power Analyzer, processed graphically and can be analysed or exported. The measurement with the 3-Phase Power Meter / 3-Phase Power Analyzer is carried out using Rogowski coils or folding current transformers.
Alternatively (if no internet connection is available), the data can be recorded in the built-in 32 GB flash memory in the form of a CSV file for further processing at a later date. An SD card adaptor is also available as an accessory, which means that the recording duration is more than one year, even when recording to the second. It is also possible to send the CSV files periodically by e-mail, upload them to a server via FTP or transfer them to the measurement platform once the measurement has been completed. Interaction with the 3-Phase Power Meter / 3-Phase Power Analyzer is mainly via Wi-Fi and web browser or via app (BLE).
Power is supplied and measured via magnetic measuring tips and connection terminals or probes. The 3-Phase Power Meter / 3-Phase Power Analyzer can be connected into any main and sub-distribution board as well as into devices and systems - the power supply does not have to be interrupted. Managing the power supply is the top priority. Without measuring consumption and recording instrumental values such as current, voltage, frequency and power, it is virtually impossible to improve efficiency. The 3-Phase Power Meter / 3-Phase Power Analyzer makes it possible to monitor the entire energy consumption and helps to reduce energy costs.
AC voltage | |
Measurement range up to | 40 ... 400 V |
Resolution | 0,01 V |
Accuracy | ±1 % of Rd. |
Alternating current AC | |
Measurement range up to | 3 ... 4800 A |
Resolution | 0.01 A |
Accuracy | ±1 % of Rd. |
Active power | |
Measurement range up to | 120 W ... 1920 kW |
Resolution | 0,01 W |
Accuracy | ±1 % of Rd |
Reactive power | |
Measurement range up to | 120 VAR ... 1920 kVAR |
Resolution | 0,01 VAR |
Accuracy | ±1 % of Rd |
Apparent power | |
Measurement range up to | 120 VA ... 1920 kVA |
Resolution | 0,01 VA |
Accuracy | ±1 % of Rd |
Power factor | |
Measurement range up to | 0 ... 1 |
Resolution | 0.01 |
Accuracy | ±1 % of Rd. |
General technical data | |
Measuring rate | 26000 Hz |
Storage medium | Internal memory |
Storage capacity | 32 GB |
Memory capacity (additional information) | separate phases: 22000 data records, summarised phases: 38000 data records |
Storage interval from | 1 s |
Storage interval to | 60 min. |
Current consumption current clamp | 100 mA DC |
Maximum cable diameter | 149 mm |
Safety standard | CAT III 300V |
Fuse(s) | 250mA, FA, IR>=30kA |
Menu language | German, English (GB), English, Spanish, French |
Protection class (device) | IP40 |
Power supply | 100 ... 240 V 50/60 Hz (+/- 10%) (between neutral conductor and phase A) |
Weight | 202 g |
Operating conditions | -5 ... 40 °C , 0 ... 80 % RH |
Storage conditions | -5 ... 40 °C , 0 ... 80 % RH |
Dimensions ( L x W x H ) | 123 x 96 x 36 mm |