Bilingual Technical Support (EN / ES)
Public Service, Military and First Responder Discount
30 Day Return Policy
2 Year Warranty
Free Standard Shipping (US)
The power analyzer redefines the standards in electrical measurement technology and offers a comprehensive range of functions for precise and detailed measurements. The power analyzer enables accurate measurements of electrical voltage, current, frequency, harmonics, harmonics and starting currents. In addition, precise power and energy measurements can be made, enabling accurate monitoring and optimisation of energy consumption.
The graphical display of waveforms and vector graphics allows users to visually capture and analyse electrical signals. These functions provide insights into the quality of the electrical current and help to identify problems in the grid. The device can also recognise and display dips, peaks or flickering in the supply network.
This wide range of measurements or the desired selection allows the integrated data logger with a generous 8 GB memory to save and archive extensive measurement data for later analyses. This ensures continuous data acquisition, which can also be time-controlled. The power analyzer is equipped with LAN and USB interfaces for convenient data transfer and remote control. These interfaces offer seamless integration of the power analyzer into existing networks and systems.
Flexible current clamps with a capacity of up to 1500 A included in the scope of delivery facilitate the measurement of high currents and enable accurate results, even in demanding applications.
The power analyzer complies with international test standards (IEC61000-4-30, 61000-4-15, 61000-4-7, EN50160), which guarantees the quality and accuracy of the measurements and ensures that it meets the demanding requirements of professional applications.
Whether you need to test the operating characteristics of transformers, lighting systems or switching electronics such as frequency converters or power supply units, our power analyzers guarantee maximum accuracy and are capable of precisely analysing even complex signal shapes.
Direct voltage DC | |
Measuring range | 1 ... 1000 V |
Resolution | 0.1 V |
Accuracy | ±0.5 % v.Mw. |
AC voltage AC | |
Measuring range | 1 ... 1000 V |
Resolution | 0.1 V |
Accuracy | ±0.5 % v.Mw. |
Alternating current AC | |
Measuring range | 1 ... 1500 A |
Resolution | 0.1 A |
Accuracy | ±3 % v.Mw. |
Power factor | |
Measurement range | 0 ... 1 |
Resolution | 0.01 |
Accuracy | ±0.03 |
Inrush current | |
Measuring range | 1 ... 1500 A AC |
Resolution | 0.1 A AC |
Accuracy | ±3 % v.Mw. |
Frequency | |
Measuring range | 42.5 ... 57.5 Hz |
Resolution | 0.01 Hz |
Accuracy | ±0.01 Hz |
Frequency | |
Measuring range | 51 ... 69 Hz |
Resolution | 0.01 Hz |
Accuracy | ±0.01 Hz |
Frequency | |
Measuring range | 385 ... 414 Hz |
Resolution | 0.01 Hz |
Accuracy | ±0.01 Hz |
Harmonic measurement (harmonics) | |
Measurement range | 1 ... 50 (ordinal number) |
Current range | 0 ... 100 % |
Voltage range | 0 ... 100 % |
Range THD | 0 ... 100 % |
General technical data | |
Display type | TFT colour display |
Display size | 2.6 inch |
Storage medium | Internal memory |
Storage capacity | 8 GB |
Storage interval of | 1 s |
Memory interval to | 60 min. |
Interface | USB, Ethernet |
Standard(s) | IEC61000-4-30, EN50160, IEC61000-4-15, IEC61000-4-7, IEC61010-1 |
Safety standard | CAT IV 600 V , CAT III 1000V |
Menu language | Turkish, English (US), Polish, Spanish, German, Chinese, Russian, French, Portuguese, Korean |
Protection class (device) | IP41 |
Power supply | 220 ... 240 V AC |
Plug type | Protective contact plug |
Weight | 1880 g |
Operating conditions | 0 ... 40 °C , 0 ... 90 % r.H |
Storage conditions | -20 ... 60 °C , 0 ... 90 % r.H |
Capacity | 3800 mAh |