Data Logging Instrument PCE-830-3-ICA incl. ISO Calibration Certificate

Order no.: PCE-830-3-ICA
GTIN (EAN):
£ 2,559.00
£ 3,070.80
ISO Calibration
price ex. (VAT / delivery)
PCE-830-3-ICA
Delivery time: 10 - 14 days
Current

Description

Data Logging Instrument with 3 phases, measures power and analyses 
harmonics with memory, interface and software

The Data Logging Instrument is used for measuring one to three phases of electrical quantities for alternating current (AC). This 3-Phase Data Logging Instrument also measures such parameters as voltage, current, frequency, harmonics and power as well as indicating, according to standard EN50160, harmonic values, interharmonics and asymmetrics. Interference, such as interruptions, leaks, overloads or transience (from 16µs) are detected with their corresponding values. The backlit LCD, with high resolution, can show up to 35 parameters simultaneously. It can have up to 3 clips attached at the same time. In data logger mode, it can save up to 17,470 readings (3 phases / 4 conductors), in a simpler set up (1 phase / 2 conductores) it can save up to 52,400 readings, split into 85 groups. All this makes the Data Logging Instrument the ideal instrument for taking measurements over long durations. Measurement values obtained can be sent to a computer and be processed with the analysis software which comes included. The device comes with everything needed to be measuring and analysing from the moment the device arrives. Although the Data Logging Instrument comes calibrated from the manufacturer, an optional laboratory calibration and certificate, that meets ISO standards, can be ordered separately with the device or when a recalibration is required.


Highlights

- Analysis of a network of 3 phases / 4 conductors, 3 phases / 3 conductors, 1 phase / 2 conductors, 1 phase / 3 conductors
- Measures effective real value (V 123 and I 123)
- Measures active power (W, KW, MW, GW)
- Measures apparent and reactive power (KVA, KVAR)
- Power Factor (PF), phase angle (Φ)
- Measures energy and work (Wh, KWh, KVARh, PFh)
- Measures current from 0.1 mA to 3000 A, allowing for the reserve power of a factory to be determined
- Large LCD that shows up to 35 parameters simultaneously (3P4W [=3 phases/4 conductors])
- CT conditions (1 to 600) and PT (1 to 3000) are programmable
- Indicates current wave forms and voltage overlap.
- 512 KB of memory with programmable intervals to save data every 2 to 3000 seconds, 17,470 readings using the system of 3 phases / 4 conductors
- Indicates wave forms, efficiency parameters, and harmonic distortion
- Backlit LCD with dot matrix
- Average power (AD in W, KW, MW)
- Maximum power (MD in W, KW, MW) with the programmable period
- Analysis of harmonic distortion up to a curvature of 99
- Indication of up to 50º form of harmonic wave
- Indication of the wave form with maximum value (1024 readings / period)
- Analysis of absolute distortion (%THD-F)
- Diagram of graphic equilibrium with parameters of a 3 phase system
- Detects up to 28 transistors (time and cycles) with a programmable threshold (%)
- Relation of 3 phases of voltage or asymmetrical current (VUR)
- Factor of 3 phases of voltage and asymmetrical current (d0%, d2%)
- USB port (optically insulated)
- Integrated timer and calendar to record data
- Maximum diameter of the electrical conductor for the amp clamp: the PCE-6801 ~30 mm / 1.2 in, PCE-6802 ~55 mm / 2.2 in, PCE-3007 ~170 mm / 6.7 in


Specification

Technical Specifications
Measurement values Measurement ranges / resolution / accuracy
PCE-830 + PCE-3007
Watts AC (50 Hz or 60 Hz, PF 0.5 up to 1)
10.0 W to 999.9 W / 0.1 W / ±1% of measurement range
1.000 kW to 9.999 kW / 0.001 kW / ±1% of measurement range
10.00 kW to 99.99 kW / 0.01 kW / ±1% of measurement range
100.0 kW to 999.9 kW / 0.1 kW / ±1% of measurement range
1000 kW to 9999 kW / 1 kW / ±1% of measurement range
PCE-830 + PCE-3007
Current AC (50 Hz or 60 Hz, auto range select, TRMS)
0 to 300 A / 0.1 A / ±1.0% of measurement range
300.0 A to 999.9 A / 0.1 A / ±1.0% of measurement range
1000 A to 3000 A / 1 A / ±1.0% of measurement range
Voltage AC (50 Hz or 60 Hz, TRMS) 20.0 V to 500.0 V / 0.1 V / ±0.5% ±5 digits
(measure between phase and neutral)
20.0 V to 600.0 V / 0.1 V / ±0.5% ±5 digits
(measure between phase and neutral)
Harmonic distortion of AC voltage 1º to 20º / 0.1% / ±1.0%
21º to 49º / 0.1% / 4% of reading ±2.0%
50º to 99º / 0.1% / 6% of reading ±2.0%
PCE-830 + PCE-3007
Harmonics
of AC current in %
1º to 10º / 0.1% / ±2%
21º to 49º / 0.1% / ±6%
50º to 99º / 0.1% / ±10%
PCE-830 + PCE-3007
Power Factor (PF)
0.000 to 1.000 / 0.001 / ±0.04
PCE-830 + PCE-3007
Phase angle (Phi)
0° to 180° / 0.1° / ±2°
PCE-830 + PCE-3007
Total harmonic distortion
0.0 to 20.0% / 0.1% / ±2%
20.0% to 100% / 0.1% / ±6% of reading ±1%
100% to 999.9% / 0.1% / ±10% of reading ±1%
Maximum measurement of AC voltage and current 50 Hz / 19 µS / ±5% ±30 digits
60 Hz / 16 µS / ±5% ±30 digits
Peak value measurement of AC voltage and current 1.00 to 99.99 / 0.01 / ±5% ±30 digits
Frequency range in automatic mode 45 Hz to 65 Hz / 0.1 Hz / 0.1 Hz
Memory 512 kB for a maximum 52,420 readings taken by 1 phase / 2 conductors
Port USB
Software and cable Included, for Windows 2000, XP, ME
Display Backlit LCD with dot matrix
Power 8 AA batteries (Mignon)
Dimensions 257 mm x 155 mm x 57 mm
10.1 in x 6.1 in x 2.2 in
Weight 1.16 kg / 2.56 lbs
Operating conditions Max. 85% relative humidity
-10º C to 50º C / +14º F to +122º F
Type of protection / standards IEC 61010, 600 V/CAT III

Delivery Scope

1 x PCE-830-3 Data Logging Instrument
3 x Amp clamps - PCE-3007
4 x Alligator clips
4 x Safety test lines (3m long)
8 x Batteries
1 x Mains adaptor
1 x Carrying case
1 x USB cablem software
1 x User's manual
1 x ISO calibration certificate

Calibration certificates are issued specifically for the customer and are excluded from the right of return.