Description

HVAC Meter PCE-779N
Compact infrared thermometer to measure surface temperatures /
Incl. thermocouple measurement / Adjustable emissivity / D
ifference measuring function / 
Tripod thread / MIN, MAX and alarm function / LED light

The infrared thermometer PCE-779N can be used for quick temperature measurements. This can be done in two different ways: either without contact or by means of a thermocouple. The infrared thermometer is suitable for nearly all surfaces. Since the infrared thermometer allows non-contacting measurement, even high temperatures can be measured from a safe distance. By means of the integrated dual laser of the infrared thermometer PCE-779N, the user can target the measuring spot very precisely.

The infrared thermometer has a variety of functions, including the MAX and MIN functions as well as the average and the difference function, which makes the infrared thermometer useful for many applications, including contacting, but also non-contacting measurements. The infrared thermometer is typically used for e. g. food monitoring, different hygiene-related controls, road construction, switch cabinet and production monitoring as well as for measuring motor temperatures.

 



Highlights

- Double laser for focusing the measuring point
- Additional thermocouple measurement
- Easy handling
- Large display - Residual value measurement
- Tripod connection
- Max min measurement
- Alarm function

Specification

  Infrared measurement Thermocouple measurement
Measurement range -60 ... 760°C / -76 ... 1400°F -64 ... 1400°C / -83.2 ... 2552°F
Accuracy
(Tobj=15 ... 35°C, Tenv= 25°C)       
± 1°C / 1.8°F  ±1% of reading
 or ±1°C / 1.8°F (higher value applies)
(measurement below Tenv= 23 ± 6°C / 42.8°F)
Accuracy
(Tenv= 23 ±3 °C)
Tobj = - 60 ... 0 ±(2+0.05/°C/°F) °C, Tobj= 0 ... 760: ±2% of reading or ± 2°C / 3.6°F  (higher value applies) ±1% of reading
or ±1°C / 1.8°F (higher value applies)
(measurement below Tenv= 23 ± 6°C / 42.8°F)
Optical resolution 30 : 1
Response time 1 s
Emissivity 0.95 (default)
0.1 ... 1.0 (adjustable)
Resolution 0.1°C / 0.18°F at -83.2 ... 999.9°C / -117.7 ... 1831.8°F... , otherwise 1°C / 1.8°F
Functions MAX, MIN, difference, average
Display LCD with backlight
Power supply 2 x AAA (Alkaline)
Battery life Without laser: at least 30 h
With laser and LED: at least 3 h
Operating conditions 0 ... 50°C / 32 ... 122°F
Laser Class 2
Weight 256 g / < 1 lb (incl. batteries)
Dimensions 119.2 x 47.5 x 171.8 mm / 4.7 x 1.9 x 6.8 in 
Note:
The technical specifications include the abbreviations Tobj and Tenv.
Tobj: object temperature
Tenv: environmental temperature

Delivery Scope

1 x HVAC Meter PCE-779N
1 x Thermocouple (max. 200°C / 392°F)
2 x Battery (AAA) 
1 x Manual