The 3-Phase Power Meter / 3-Phase Power Analyzer is used for measuring one to three phases of electrical quantities for alternating current (AC). This 3-Phase-Power Meter also measures such parameters as voltage, current, frequency, harmonics and power as well as indicating, according to standard EN50160, harmonic values, interharmonics and asymmetrics. Interference, such as interruptions, leaks, overloads or transience (from 16µs) are detected with their corresponding values. The backlit LCD, with high resolution, can show up to 35 parameters simultaneously. It can have up to 3 clips attached at the same time. In data logger mode, it can save up to 17,470 readings (3 phases / 4 conductors), in a simpler set up (1 phase / 2 conductores) it can save up to 52,400 readings, split into 85 groups. All this makes the 3-Phase-Power Meter the ideal instrument for taking measurements over long durations. Measurement values obtained can be sent to a computer and be processed with the analysis software which comes included. The device comes with everything needed to be measuring and analysing from the moment the device arrives. Although the 3-Phase-Power Meter comes calibrated from the manufacturer, an optional laboratory calibration and certificate, that meets ISO standards, can be ordered seperately with the device or when a recalibration is required.
Technical specifications | |
Measurement values | Measurement ranges / resolution / accuracy |
PCE-830 + PCE-6801 Watts AC (50 or 60Hz, PF 0.5 up to 1) |
5.0 to 999.9W / 0.1W / ±1% ±0.8W 1.000 to 9.999kW / 0.001kW / ±1% ±8W 10.00 to 99.99kW / 0.01kW / ±1% ±80W 100.0 to 999.9kW / 0.1kW / ±1% ±0.8kW 1000 to 9999kW / 1kW / ±1% ±8kW |
PCE-830 + PCE-6801 Current AC (50 or 60Hz, auto range select, TRMS) |
0.04A to 1A / 0.001A / ±0.5% ±0.05A 0.4A to 10.0A / 0.01A / ±0.5% ±0.05A 4A to 100.0A / 0.1A / ±1.0% ±0.5A |
Voltage AC (50 or 60Hz, TRMS) | 20.0 to 500.0V / 0.1V / ±0.5% ±5 digits (measure between phase and neutral) 20.0 to 600.0V / 0.1V / ±0.5% ±5 digits (measure between phase and neutral) |
Harmonic distortion of AC voltage | 1 to 20º / 0.1% / ±1.0% 21 to 49º / 0.1% / 4% of reading ±2.0% 50 to 99º / 0.1% / 6% of reading ±2.0% |
PCE-830 + PCE-6801 Harmonics of AC current in % |
1 to 20º / 0.1% / ±0.2% of reading ±1.0% 11 to 20º / 0.1% / ±2% of reading ±1.0% 21 to 50º (A)/ 0.1% / ±5% of reading ±1.0% 21 to 50º (mA)/ 0.1% / ±10% of reading ±1.0% 51 to 99º / 0.1% / ±35% of reading ±1.0% |
PCE-830 + PCE6801 Power Factor (PF) |
0.00 to 1.00 / 0.01 / ±0.04 |
PCE-830 + PCE6801 Phase angle (Phi) |
-180° to 180° / 0.1° / ±1° |
PCE-830 + PCE-6801 Total harmonic distortion |
0.0 to 20.0% / 0.1% / ±1% 20.0 to 100% / 0.1% / ±3% of reading ±5% 100 to 999.9% / 0.1% / ±10% of reading ±10% |
Maximum measurement of AC voltage and current | 50Hz / 19µS / ±5% ±30 digits 60Hz / 16µS / ±5% ±30 digits |
Peak value measurement of AC voltage and current | 1.00 to 99.99 / 0.01 / ±5% ±30 digits |
Frequency range in automatic mode | 45 to 65Hz / 0.1Hz / 0.1Hz |
Memory | 512kB for a maximum 52,420 readings taken by 1 phase / 2 conductors |
Port | USB |
Software and cable | included, for Windows 2000, XP, ME |
Display | backlit LCD with dot matrix |
Power | 8 AA batteries(Mignon) |
Dimensions | 257 x 155 x 57mm / 10.1 x 6.1 x 2.2 in |
Weight | 1160g / 40.9 oz |
Operating conditions | max. 85% relative humidity / -10 ... 50ºC / 14 ... 122 °F |
Type of protection / standards | IEC 61010, 600 V/CAT III |
1 x PCE-830 3-Phase Power Meter / 3-Phase Power Analyzer
3 x Amp clamps - PCE-6801
4 x Alligator clips
4 x Safety test lines (3m long),
8 x Batteries
1 x Mains adaptor
1 x Carrying case
1 x USB cablem software
1 x User's manual
1 x ISO calibration certificate
Calibration certificates are issued specifically for the customer and are excluded from the right of return.